Workspacecooling for Evaporative Cooling French Language version of Work Space Cooling

 

Factory cooling
Commercial cooling
Industrial cooling
Portable industrial cooling
Mobile cooling
Suppliers of EcoCooling Evaporative Cooling Units

Sizing of Systems

Air Changes Method

This method calculates the number of coolers required based on the number of air changes per hour with a given working volume.
The working volume is that underneath the discharge of the plenum chambers as shown by the blue shaded area in the diagram below.

Typical air changes per hour are:

  Light manufacturing
eg Warehouse, packing area
10
  Normal manufacturing
eg Machine shop, assembly area
17

Heavy manufacturing
eg Injection moulding, welding shop
25

Extreme conditions
eg Bakery, forge
35

Air changes per hour

Example calculation

A bakery is 20m x 24m and it is proposed to fit ECP plastic external units with a minimum plenum discharge height of 3.5m.

Volume of working area: 20 x 24 x 3.5 = 1680m3

Target air changes per hour: 30

Target air flow per hour: 30 x 1680 = 50,400m3/hr

Air flow rate of ECP16000 13,000 m3/hr@150Pa

Nominal number of coolers required 50,400 / 13,000 =3.8 = 4 coolers

Therefore the proposal would be 4 ECP16000 coolers together with balanced extract to maintain a small positive pressure.

go to top of page

 
Work Space Cooling are specialists in the cooling of industrial and commercial premises
ACHIEVE UP TO 35 KW of COOLING for 1KW OF ELECTRICITY USED
Site created by: Wyehead Design ©2005